Abstract
Pool boiling on confined and unconfined tube columns was investigated. A model to predict bulk void fraction in a confined tube column was developed and validated experimentally, returning a mean predictive accuracy of 12.5%. A semi-empirical model was also developed from bubble plume images to evaluate bulk void fraction in an unconfined plume around a tube column. Within an unconfined plume, void fraction increases monotonically with column height, indicating that a column height exists beyond which the mean column heat transfer coefficient is adversely affected by dryness. Pool boiling experiments were undertaken in Novec 649 to investigate the effects of external confinement, tube spacing, and column height on heat transfer. Increasing the column height in a column showed an initial decline in power density to a constant at ∼30 MW m−3. A tube void fraction threshold was identified as changing the location of critical heat flux from the bottom tube to the top tube in a column, and to cause a deterioration in tube heat transfer coefficient at high heat fluxes.
Original language | English |
---|---|
Article number | 118733 |
Journal | International Journal of Heat and Mass Transfer |
Volume | 145 |
DOIs | |
Publication status | Published - 20 Sept 2019 |
Keywords
- Bubble plume
- Nucleate pool boiling
- Passive cooling
- Tube bundles
- Void fraction